J100 and j101, Table 38 qs871 j2 signal description, Table 39 qs871 j3 signal description – GE Industrial Solutions Pulsar Plus Controller User Manual

Page 108: Table 40 qs871 j100 and j101 signal description

Advertising
background image

Pulsar Plus Controller Family

Issue 7 December 2011

108

Table 37 QS871 J1 Signal Description

6

OS

Open String (OS) alarm input for external battery disconnect switch; Alarms on
closure to the non-grounded “Battery” side of the DC bus (-48V).

7

FAJ

General purpose Fuse Alarm Major (FAJ) alarm input; Major alarm on closure to
the non-grounded “Battery” side of the DC bus (-48V).

8

SHLF_ID3

Signal used for identifying the board. Pulled up or down on board accordingly in
the factory.

9

RS485+

B Inverting Driver Output / Inverting Receiver Input

10

RS485-

A Non-inverting Receiver Input/ Non-inverting Driver Output

J2
Provides the contactor management interface for control and LVD status.

Table 38 QS871 J2 Signal Description

Pin #

Signal Name

Signal Description

1

LVD_COIL

Positive voltage applied to Low Voltage Disconnect Coil. Connect to positive
side of contactor coil.

2

LVD_COILRTN Contactor coil return to VBUS- potential through circuitry. Connect to most

negative side of Contactor coil, other side of coil connected to VBus(+).

3

LVD _NC

Normally Closed contactor status monitor. Closed to LVD_C when contactor is
open. Connect signal to NC pin of micro- switch of Contactor.

4

LVD_NO

Normally Open contactor status monitor indicator. Closed to LVD_C when
contactor is closed. Connect signal to NO pin of micro-switch of contactor.


Note: The common or return of the micro switch for these signals must be attached to Vbus- in the system
outside of this board.
J3
Connection that provides field access to External Auxiliary Fuse Alarm Major and the Remote LVD input.

Table 39 QS871 J3 Signal Description

Pin # Signal Name

Signal Description

1

Remote LVD

External contact closure for remote disconnecting attached LVD; Disconnects
LVD on a dry contact closure to Remote LVD Return when feature is enabled.

2

Remote LVD
Return

Protective (PTC or resistive) return to NE common for External Remote LVD
contact closure input signal.

3

Aux_Alarm

General purpose Fuse Alarm Major (FAJ) alarm input; Major alarm on closure
to the non-grounded “Battery” side of the DC bus Battery (-48V).

J100 and J101
Provides connectivity to the RS485 GP rectifier/converter bus as well as a pass through to the next RS485
connected device.

Table 40 QS871 J100 and J101 Signal Description

Pin # Signal Name

Signal Description

1

RS485+

B Inverting Driver Output / Inverting Receiver Input

2

RS485-

A Non-inverting Receiver Input/ Non-inverting Driver Output

3

RS485REF

RS485 Reference/return. Pass-through on this board.

4

No Connection

5

-

Connects between J101.5 and J100.5. Connection reserved for1-Wire
communication signal in the system.

6

-

Connects between J101.6 and J100.6. Connection reserved for1-Wire +5V
signal in the system.