Table D-3 48V Battery Related Items Defaults

Category

Description

Range

Valve-Reg

Flooded

Li_ELiTE

NiCd

Li-LMP

obj,attr

Voltage Settings

Rectifier Float Selective High Voltage
Shutdown

-50 to -60V

58.50

58.50

58.50

58.50

58.50

GM1,FSD

High Float Voltage Major Alarm

-50 to -60V

57.00

57.00

57.00

57.00

57.00

HVA1,FTH

High Float Voltage Minor Alarm

-50 to -60V

56.00

56.00

56.00

56.00

56.00

HFV1,FTH

Rectifier/System Float Voltage

-42 to -56.5V

54.48

52.08

54.48

54.40

54.48

GM1,FSP

Battery on Discharge Float Alarm

-46 to -55V

51.00

50.00

53.00

51.00

51.00

BDA1,FTH

Very Low Float Voltage Alarm

-40 to -51V

46.00

46.00

46.00

46.00

46.00

VLA1,THR

Rectifier On Threshold

-40 to -51V

44.00

44.00

44.00

44.00

44.00

DC1,ROT

Battery Disconnect

LV Battery Disconnect

1=Enabled

0=Disabled

1

1

0

1

0

CN1,ENA

LV Battery Disconnect Voltage

-39.0 to -50V

42.00

42.00

42.00

42.00

42.00

CN1,DTH

LV Battery Reconnect Voltage

-39.0 to -55V

48.00

48.00

48.00

48.00

48.00

CN1,RTH

Batteries

Cells Per String

0 to 75

24

24

24

24

24

DC1,CPS

String End Of Discharge Voltage

-40.25 to -

48.75V

42.00

42.00

42.00

42.00

42.00

BR1,CEV

Recharge Current Limit Feature

1=Enabled

0=Disabled

0

0

0

0

0

BR1,CLE

Recharge Current Limit Value

5 to 1000A

50

50

25

25

25

BR1,CLT

Boost Maximum Duration

1 to 80 Hours

1

1

1

1

1

BS1,TMD

Voltage Imbalance Detect

1.5V to 3.0V

1.7

1.7

1.7

2.0

1.7

BR1,SCV

High Temperature Battery Disconnect

30 to 90

o

C

75

75

75

75

75

BR1,TTH

High Battery Temperature

30 to 85

o

C

55

55

55

55

85

BTHA1,THR

Battery Slope

Compensation

Slope Thermal Compensation (STC)

1=Enabled

0=Disabled

1

0

0

0

0

SC1,STT

High Temperature Voltage Step Down

45 to 85

o

C

75

75

75

75

75

SC1,SPT

High Temperature Compensation Stop

30 to 55

o

C

55

55

55

55

55

SC1,UTT

High Temperature Decrease Rate

1-10mV/

o

C per

cell

3

3

3

3

3

SC1,USP

Nominal Temperature (No Temp Comp)

15 to 30

o

C

25

25

25

25

25

SC1,NTT

Low Temperature Compensation Feature

1=Enabled

0=Disabled

0

0

0

0

0

SC1,RVE

Low Temperature Compensation Stop

-5 to 20

o

C

0

0

0

0

0

SC1,LTT

Low Temperature Decrease Rate

1-10mV/

o

C per

cell

3

3

3

3

3

SC1,LSP

Battery Discharge Test

Timed Test Alarm Voltage Threshold

-36 to -48V

44.00

44.00

46.00

44.00

44.00

BR1,TEV

Rectifier Voltage During Battery Test

-42.00 to -52V

42.00

42.00

42.00

42.00

42.00

BR1,BTV

Battery Boost

Boost Rectifier High Voltage Shutdown

-52 to -60V

58.50

58.50

58.50

58.50

58.50

GM1,BSD

Boost High Voltage Major Alarm

-50 to -60V

57.0

58.5

57.0

57.0

57.0

HVA1,BTH

Boost High Voltage Minor Alarm

-50 to -60V

56.0

58.0

56.0

56.0

56.0

HFV1,BTH

Boost Voltage

-48 to -58V

55.2

57.0

54.5

54.4

54.5

GM1,BSP

Boost Battery on Discharge Alarm

-46 to -55V

51.0

50.0

53.0

51.0

51.0

BDA1,BTH

Advertising