Table 56 T1.317 Battery Reserve Management Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

br1,nvm

Number of mid-cell V present

d

br1,ntm

Number of temperatures present 

d

br1,scd

Battery voltage imbalance
detection enable

number 0=disable,1=enable

(Automatically enabled
when mid cell V monitor
present)

br1,scv

Battery imbalance threshold

number 1.5-3.0V

Table 57 T1.317 Battery Type Definition Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

btnn,des

Description

Text

Battery Configuration 1

btnn,bty

Battery Type

Text

Up to 14 characters

btnn,btc

Battery Class

Text

FLOODED, SEALED, NICD,
LI_LMP, LI_ELITE

btnn,cap

Capacity

Number number

Where n stands for battery type number (1 thru 25)

Table 58 T1.317 Boost Management Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

bs1,ide

Identifier

Text

BS1

bs1,des

Description

Text

Boost Control 1

bs1,stt

State

Text

QRCT, MANUAL, BTP, TIMED
AU-TO, OFF

bs1,atm

Auto Mode

Text

OFF, QRCT, TIMED

bs1,tmd

Timed Manual Duration

Number 1-80 hours

bs1,amf

Auto Multiplication Factor

Number 0.1-9

bs1,cta

Current Term Current Thresh

Number 1-999A

Table 59 T1.317 Disconnect Contactor Control Related Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

cnx,ide

Identifier

number CN1, CN2, CN3, CN4

cnx,des

Description

number Contactor 1

cnx,stt

Status

text

NONE, DISCON, CONNECT,
FAILED

cnx,ena

Control enable

0=disable,1=enable

cnx,dth

Disconnect threshold

number 19-25V or 39-50V

cnx,ddy

Disconnect delay

number 0-300 minutes

cnx,dam

Disconnect automode

text

0=“NONE”
1=“VOLTAGE”
2= “VOLTAGE+TIME”

cnx,dtm

Disconnect remaining time

number >0 means going to

disconnect

cnx,rth

Reconnect threshold

number 19.5-27V or 39-55V

cnx,rdy

Reconnect delay

number 0-300 seconds

cnx,ram

Reconnect automode

text

0=“NONE”
1=“VOLTAGE”
2=“VOLTAGE+TIME”

cnx 4,rtm

Reconnect remaining time

number >0 means going to reconnect

The contactors are identified as follows: