7-18 Communicating with a PLC-5 Adapter Channel

Write ladder logic in the supervisory controller to monitor the rack-fault bits
for the rack that the adapter-mode controller channel is emulating to
determine the status of the remote I/O link.

Monitoring the Status of the Supervisory Controller

The adapter-mode controller channel reserves bits 10-17 of the first word of
the input destination file for status. These bits tell the adapter-mode controller
channel the status of the supervisory controller and the integrity of the remote
I/O communication link.

When this Bit(s)

Is

It Indicates

10 octal (8 decimal)

and

15 octal (13 decimal)

0

adapter-mode controller is in run mode

10 octal (8 decimal)

and

15 octal (13 decimal)

1

adapter-mode controller is in program or test mode

When this Bit(s)

Is

It Indicates that the Adapter-Mode Controller

10 octal (8 decimal)

1

detects a communication failure or receives a reset command
from the supervisory controller

will be set if either bit 11 octal (9 decimal) or bit 15 octal (13
decimal) is set

11 octal (9 decimal)

1

receives a reset command from the supervisory controller
(controller in program or test mode)

13 octal (11 decimal) 1

detects that the supervisory controller has powered up; this bit
is reset with the first communication from the supervisory
controller

15 octal (13 decimal) 1

detects a communication failure (e.g., no communication
activity on the remote I/O communication link within the last
100 ms)

00

03

04

07

10

13

14

17

00

03

04

07

08

11

12

15

Word

0

Adapter Channel’s Input Destination File

Example Integer File

Scanner’s Output Image Table

Status of supervisory
processor

Not used by
adapter channel.