B-6 Processor Status File

30

You tried to jump to one too many nested subroutine files

Non-recoverable

The fault routine will be executed
but cannot clear major fault bit 2.

31

You did not enter enough subroutine parameters

32

You jumped to an invalid (non-ladder) file

33

You entered a CAR routine file that is not 68000 code

34

You entered a negative preset or accumulated value in a timer instruction

Recoverable

35

You entered a negative time variable in a PID instruction

36

You entered an out-of-range setpoint in a PID instruction

37

You addressed an invalid module in a block-transfer, immediate input, or immediate output
instruction

38

You entered a RET instruction from a non-subroutine file

Non-recoverable

The fault routine will be executed
but cannot clear major fault bit 2.

39

FOR instruction with missing NXT

40

The control file is too small for the PID, BTR, BTW, or MSG instruction

Recoverable

41

NXT instruction with missing FOR

Non-recoverable

The fault routine will be executed
but cannot clear major fault bit 2.

42

You tried to jump to a non-existent label

43

File is not an SFC

44

Error using SFR. This error occurs if:

• you tried to reset into a simultaneous path
• you specified a step reference number that is not found or is not tied to a step (it is a transition)
• the previous SFR to a different step is not complete

45

Invalid channel number entered

Recoverable

46

Length operand of IDI or IDO instruction is greater than the maximum allowed

47

SFC action overlap. An action was still active when the step became re-activated

Non-recoverable. The fault
routine will be executed but
cannot clear major fault bit 2.

This
Fault
Code

Indicates this Fault

And the Fault Is