Understanding controller-detected major faults, Understanding controller-detected major faults -2 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 240

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

15-2 Preparing Fault Routines

returns to the current ladder program file if the controller can recover
from the fault

enters fault mode if the controller cannot recover from the fault

For example, this rung includes an instruction that causes a major fault:

Understanding
Controller-Detected Major
Faults

In general:

[

A

B

C

Causes a
major fault

[

In this example, the processor runs the fault routine after detecting the fault. If the
fault routine resets the faulted bits, the processor returns to the next instruction in
the program file that follows the one that faulted and continues executing the
remainder of the rung.
If you do not program a fault routine for fault B, the processor immediately faults.

If the Controller Detects a

It Sets

major fault

a major fault bit and resets I/O

memory loss fault

outputs in 1771-ASB remote I/O racks and/or 1771-ALX
extended-local I/O racks are set according to their last
state switch setting

The outputs remain in their last state or they are
de-energized, based on how you set the last state switch
in the I/O chassis.

IMPORTANT

In the PLC-5 controller-resident chassis, outputs are reset
regardless of the last state switch setting when one of the
following occurs:

controller detects a major fault

you set a status file bit to reset a local rack

you select program or test mode