Placing System Hardware

Using This Chapter

Determining the Proper
Environment

Place the controller in an environment with conditions that fall within these
guidelines:

Separate your programmable controller system from other equipment and
plant walls to allow for convection cooling. Convection cooling draws a
vertical column of air upward over the controller. This cooling air must not
exceed 60° C (140° F) at any point immediately below the controller. If the air
temperature exceeds 60° C, install fans that bring in filtered air or recirculate
internal air inside the enclosure, or install air-conditioning/heat-exchanger
units.

To allow for proper convection cooling in enclosures containing a
controller-resident chassis and remote I/O chassis, follow these guidelines.

For Information About

Go to Page

Determining the proper environment

3-1

Protecting your controller

3-3

Avoiding electrostatic damage

3-3

Laying out your cable raceway

3-4

Laying out your backpanel spacing

3-5

Grounding your system

3-6

Environmental Condition Acceptable Range

Operating temperature

0 to 60° C (32 to 140° F)

Storage temperature

-40 to 85° C (-40 to 185° F)

Relative humidity

5 to 95% (without condensation)