4-16 Addressing I/O and Controller Memory

Addressing

Valid formats for addressing data files are:

For more information about entering addresses, see the documentation for
your programming software.

Specifying I/O Image Addresses

The I/O image address corresponds to the physical location of the I/O circuit
in the I/O chassis:

If You Want to Access

Use this Addressing Format

And See Page

Input or output bit in the I/O image table

I/O image address

4-16

Bit, word, sub-member, data block, file, or I/O image bit

Logical address

4-17

A component within a logical address by substituting the
value in another address

Indirect address

4-18

An address offset by some number of elements

Indexed address

4-20

A substitute name for an address

Symbolic address

4-21

a

I/O address identifierI = input device
O = output device

bb

I/O Rack numberPLC-5/11, -5/20, -5/20E00-03 (octal)
PLC-5/3000-07 (octal)
PLC-5/40, -5/40L, -5/40E00-17 (octal)
PLC-5/60, -5/60L, -5/80, -5/80E00-27 (octal)

c

I/O Group number0-7 (octal)

dd

Terminal (bit) number00-17 (octal)

To Specify this
Address

Example

Input Image Bit

Output Image Bit

I for input
2-digit I/O rack Number
I/O group number (0-7)
Input number (0-7, 10-17)

I

:

0

1

7

/

0

1

O for output
2-digit I/O rack Number
I/O group number (0-7)
Output number (0-7, 10-17)

O

:

0

1

7

/

0

1