Publication 1785-UM012D-EN-P - July 2005

Processor Status File B-9

S:13-S:24

This Word:

Stores

S:13

Program file where fault occurred

S:14

Rung number where fault occurred

S:15

VME status file

S:16

I/O status File

S:17Minor fault (word 2)
See also S:10.

S:17/00

BT queue full to remote I/O

S:17/01

Queue full - channel 1A; maximum remote block-transfers used

S:17/02

Queue full - channel 1B; maximum remote block-transfers used

S:17/03

Queue full - channel 2A; maximum remote block-transfers used

S:17/04

Queue full - channel 2B; maximum remote block transfers used

S:17/05

No modem on serial port

S:17/06

• Remote I/O rack in local rack table or
• Remote I/O rack is greater than the image size. This fault can also be

caused by the local rack if the local rack is set for octal density scan
and the I/O image tables are smaller than 64 words (8 racks) each.

S:17/07

Firmware revision for channel pairs 1A/1B or 2A/2B does not
match controller firmware revision

S:17/08

ASCII instruction error

S:17/09

Duplicate node address

S:17/10

DF1 master poll list error

S:17/11

Protected controller data table element violation

S:17/12

Protected controller file violation

S:17/13

Using all 32 ControlNet MSGs

S:17/14

Using all 32 ControlNet 1771 READ and/or 1771 WRITE CIOs

S:17/15

Using all 8 ControlNet Flex I/O CIOs

S:18

Controller clock year

S:19

Controller clock month

S:20

Controller clock day

S:21

Controller clock hour

S:22

Controller clock minute

S:23

Controller clock second

S:24

Indexed addressing offset

S:25

Reserved