Addressing I/O and Controller Memory 4-3

Choosing an Addressing
Mode

For each I/O chassis in your system, you must define how many I/O chassis
slots make up an I/O group (1 word each in the input image table and output
image table); this choice is the chassis’ addressing mode. Choose from among
these available modes:

When you place your I/O modules in the I/O chassis slots, the module’s
density determines how quickly I/O groups form. For example, let’s choose
1-slot addressing and see how 8-, 16-, and 32-point I/O modules fill controller
memory.

2-slot addressing

2 I/O chassis slots = 1 I/O group = 1 input image word and 1 output image
word = 16 input bits and 16 output bits.

1-slot addressing

1 I/O chassis slot = 1 I/O group = 1 input image word and 1 output image
word = 16 input bits and 16 output bits.

1/2-slot addressing

1/2 of an I/O chassis slot = 1 I/O group = 1 input image word and 1 output image
word = 16 input bits and 16 output bits.

x

x

x

x

x

x

x

x

Output Image Table

Word #

Input Image Table

Word #

16 bits input

16 bits output

16 bits input and 16 bits output

16 bits input and 16 bits output

Controller memory
Rack x