Transferring Block Data

In addition to discrete data, the controller can also exchange block data with
remote I/O. Block-transfer instructs the controller to interrupt normal I/O
scanning and transfer as many as 64 words of data to/from a selected I/O
module. The figure below shows how the scanner-mode controller handles a
block-transfer.

Block-Transferring Data to Controller-Resident Local, Extended-Local, and

Remote I/O

15299

Rack 7

Controller-

Rack 0

Remote I/O
Scan

Remote I/O

Program

Scan

Rack 6

Rack 5

One transfer per
I/O scan

One transfer per
I/O scan

One transfer per
I/O scan

BTR or BTW Data

BT
Requests

Q

A

BTR or BTW Data

BT Requests

Q

A

BTR or BTW Data

BT Requests

Q

A

BTR or BTW Data

BT
Requests

Q

A

Q = Queue
A = Active

Buffer

I/O Scan

Multiple
Block Transfers

Q

A

One transfer per
I/O scan

BTR or BTW Data

Extended-
Local
I/O Scan

Adapter

Adapter

Adapter

BT Requests

Interrupt from STI or Fault Routine
The adapter used in the remote I/O scan is the 1771-ASB.
The adapter used in the extended-local I/O scan is the 1771-ALX.

Resident

Local

Local

Local

Rack 4

Racks 2
and 3

Rack 1

Adapter

Adapter

Adapter

per I/O Scan

Logic

Scan

1

1

1

1

1

1

2

3

2

3

Advertising