Addressing block-transfer modules, Addressing summary – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 51

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

Addressing I/O and Controller Memory 4-7

Addressing
Block-Transfer Modules

Block-transfer modules occupy 8 bits in the controller’s I/O image table.
Since all block-transfer modules are bidirectional, they cannot be used to
complement either input or output modules.

Addressing Summary

Use this table as a quick reference for addressing.

To Address

Use

single slot modules assigned I/O rack and group number of the slot in which the

module resides and 0 for the module number

When using 1/2-slot addressing, use the assigned rack
number and the lowest group number and 0 for the module
number.

double-slot modules assigned rack number and the lowest group number and 0 for

the module number

Addressing
Mode

Guidelines

2-slot

Two I/O module slots = 1 group

Each physical 2-slot I/O group corresponds to one word (16 bits) in the input image table and
one word (16 bits) in the output image table

When you use 16-point I/O modules, you must install as a pair an input module and an output
module in an I/O group; if you use an input module in slot 0, you must use an output module in
slot 1 (or it must be empty). This configuration gives you the maximum use of I/O.

You cannot use a block-transfer module and a 16-point module in the same I/O group because
block-transfer modules use 8 bits in both the input and output table. Therefore, 8 bits of the
16-point module would conflict with the block-transfer module.

You cannot use 32-point I/O modules.

Assign one I/O rack number to eight I/O groups.

1-slot

One I/O module slot = 1 group

Each physical slot in the chassis corresponds to one word (16 bits) in the input image table and
one word (16 bits) in the output image table

When you use 32-point I/O modules, you must install as a pair an input module and an output
module in an even/odd pair of adjacent I/O group; if you use an input module in slot 0, you must
use an output module in slot 1 (or it must be empty). This configuration gives you the maximum
use of I/O.

Use any mix of 8- and 16-point I/O modules, block-transfer or intelligent modules in a single I/O
chassis. Using 8-point modules results in fewer total I/O.

Assign one I/O rack number to eight I/O groups.

1/2-slot

One half of an I/O module slot = 1 group

Each physical slot in the chassis corresponds to two words (32 bits) in the input image table
and two words (32 bits) in the output image table

Use any mix of 8-, 16-, and 32-point I/O or block-transfer and intelligent modules. Using 8-point
and 16-point I/O modules results in fewer total I/O.

With the controller-resident local rack set for 1/2-slot addressing, you cannot force the input
bits for the upper word of any slot that is empty or that has an 8-point or 16-point I/O module.
For example, if you have an 8-point or a 16-point I/O module in the first slot of your local rack
(words 0 and 1 of the I/O image table, 1/2-slot addressing), you cannot force the input bits for
word 1 (I:001) on or off.

Assign one I/O rack number to eight I/O groups.

Advertising