Controller time, C-11 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 297

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

Maximizing System Performance C-11

To optimize your system layout for block-data transfers, use an arrangement
similar to the following:

Controller Time

The controller time is the time needed to process the inputs and set the
corresponding outputs. This controller time varies for different controllers
and is based on input buffering, program scan, etc.

PLC

Adapter

BT

BT

Adapter

Adapter

With this arrangement, a block-transfer to each BT
module can occur in a single discrete I/O scan.

Maximum scan time

Minimum time to complete
a block-transfer to all modules

= 3 discrete scans + 3 block-transfers

= 3D + 3BT

= 1 (3D + 3BT)

= 3D + 3BT

BT

System Optimized for Block-Data Transfer

In a PLC-5 system, inputs are buffered between the I/O image table and the remote I/O
buffer. The movement of inputs from the remote I/O buffer to the input buffer is
asynchronous to the movement of data from the input buffer to the input image table.

a b

Adapter

Adapter

Adapter

IOT (x)

IIN (y)

x

y

Rack 3

Rack 2

Rack 1

Housekeeping

Scan

Logic

Processor-
Resident
Rack

Data
Exchange

Immediate I/O

Data Exchange

I/O Image
Table

Remote I/O
Buffer

Program Scan Loop

Remote I/O Scan Loop

Update
I/O image
from input
buffer

a
write outputs

b
read inputs

Input
Buffer

1