Chapter 4 - addressing i/o and controller memory, Addressing i/o and controller memory, Using this chapter – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 45: I/o addressing concept, Chapter 4, Using this chapter -1 i/o addressing concept -1, Chapter, Using this chapter i/o addressing concept

Advertising
background image

1

Publication 1785-UM012D-EN-P - July 2005

Chapter

4

Addressing I/O and Controller Memory

Using This Chapter

I/O Addressing Concept

Since the main purpose of a programmable controller is to control inputs and
outputs of field devices like switches, valves, and thermocouples, these inputs
and outputs must occupy a location in the controller memory so that they can
be addressed in your control program. Each terminal on an input or output
module that can be wired to a field device occupies a bit within controller
memory. The part of controller memory that houses I/O addresses is the
input image table
and the output image table.

I/O addressing helps connect the physical location of an I/O module terminal
to a bit location in the controller memory. I/O addressing is just a way to
segment controller memory. The segmentation is as follows:

For Information About

Go to Page

I/O addressing concept

4-1

Choosing an addressing mode

4-3

Addressing block-transfer modules

4-7

Addressing summary

4-7

Assigning racks

4-8

Understanding PLC-5 controller memory

4-10

Addressing

4-16

Effectively Using I/O Memory

4-24

Classification

Term

Relation to Controller Memory

A specific terminal on an I/O module that
occupies a space in controller memory

terminal or
point

The density of an I/O module, i.e., 8-point, 16-point, 32-point, directly
relates to the amount of memory (bits) the module occupies in controller
memory. For example, a 16-point input module occupies 16 bits in the
controller’s input image table.

I/O terminals that when combined occupy 1
word in controller’s input image table and 1
word in the controller’s output image table.

I/O group

16 input bits = 1 word in controller’s input image table
16 output bits = 1 word in the controller’s output image table

Controller memory needs to be grouped so that
related I/O groups can be considered a unit.

I/O rack

128 input bits and 128 output bits, or8 input words and 8 output words,
or 8 I/O groups

Each PLC-5 controller has a finite amount of racks it can support. For
example, a PLC-5/30 can support 8 I/O racks.
The controller always occupies at least one I/O rack for itself, rack 0 by
default.

Advertising