Programming Considerations 13-9

To ensure that the received BTR data table file has been properly updated
before you use the data, do the following:

1. Enable the input conditions of the BTR rung.

2. Wait for the BTR done bit to be set.

3. Allow time for housekeeping to force and send the changed data from

the block-transfer data buffer to the block-transfer data table file.

To ensure that the intended BTW data table file was properly transferred, do
the following:

1. Change the data in the block-transfer output data table.

2. Allow time for housekeeping to force and send the changed data from

the block-transfer output data table file to the block-transfer data buffer.

3. Enable the BTW

OTL

BTR data valid

BT10:0

BTR.DN detected

DN

OTE)

/

If BTR data is not valid

BTR

Rack

Group
Module

Control Block

Data File

Length
Continuous

01

4
0

BT10:0

N9:0

6

N

BTR data valid

any logic
accessing
the BTR data or
copy data to
another file

BTR data valid

OTU)

[END OF FILE]

After the BTR done bit is set, the valid data in the BT data buffer
is copied to the BTR data table file during housekeeping.

BTR DN detected

BTR data valid

41401