Publication 1785-UM012D-EN-P - July 2005

Communicating with Extended-Local I/O 8-5

Discrete Data Transfer

The time that it takes to scan extended-local I/O chassis is added to the
housekeeping time as shown in the following figure.

PLC-5/40L and -5/60L Extended-Local I/O Scan Time

Adapter

Adapter

Adapter

Housekeeping

Rack 3

Rack 2

Rack 1

Remote I/O
Buffer

Logic
Scan

Remote I/O

Scan

Program Scan

IOT (x)

IIN (y)

Immediate I/O

Processor-

Rack

Resident

I/O Image

Table

Data

Exchange

Update
I/O image

Extended
-local I/O

Data

Exchange

Data

Exchange

a

b

a
write outputs

b
read inputs

x

y

x

y

Data exchange occurs during housekeeping. Outputs are written to
and inputs read from the I/O image table during the logic scan.

IIN and IOT data transfer directly to and
from I/O modules extended-local I/O chassis.

The processors scan the extended-local I/O chassis during the
housekeeping portion of the program scan. Extended-local I/O
discrete data is exchanged between the processor’s data table
image and the I/O in the extended-local I/O chassis.

1

1

+

Processor
Checks

Remote
I/O Buffer
Update

Processor
Resident
I/O Update

Extended-
Local I/O
Scan

Housekeeping

Program Scan

Logic Scan