Communicating with Devices on a Serial Link 10-9

Configure Channel 0 as a Slave Station

To configure channel 0 for DF1 slave communication, use the system mode
configuration screen in your programming software.

configure the serial
communications as
system slave

specify the details

This Field

Specifies:

Configure by Doing the Following

Diagnostic file

The file containing the channel’s
status information

Enter an integer file number (10-999).

ATTENTION: Assign a unique diagnostic file to each channel. Do not
assign a diagnostic file that is the I/O status file you assigned or any
other used integer file. Unpredictable machine action can result.

Important: You must define a diagnostics file for a channel configured
for anything but unused (even if you are not using the channel) if you want
to get status information for that channel.

Enable

Whether the remote mode change
option is enabled

Select ENABLED or DISABLED.

Mode attention char.

The attention character for the system
mode or the user mode character for a
remote mode change

Enter a character. If the attention character you want to use is a control
character, specify the ASCII equivalent.

System mode char.

The character for the mode attention
character (above)

Enter an attention character. If the attention character you want to use is
a control character, specify the ASCII equivalent.

When the controller encounters the attention character and the system
mode character, the controller sets channel 0 communication to system
mode. The remote mode change option must be ENABLED.