Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 288

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

C-2 Maximizing System Performance

Effects of False Logic versus True Logic on Logic Scan Time

The rung below—which changes states from one program scan to the next—
will change your scan time by about 400

µ

s.

Other instructions may have a greater or lesser effect.

Effects of Different Input States on Logic Scan Time

You can write your logic so that it executes different rungs at different times,
based on input conditions. The amount of logic executed in logic scans causes
differences in program scan times. For example, the simple differences in rung
execution in the following example cause the program scan to vary.

NATURAL LOG

Source

Dest

N7:0

F8:20

I:000

00

LN

5

1.609438

If I:000/00 is

Then the Rung is

On

True, and the controller calculates the natural log.
A natural log instruction takes 409

µ

s to execute.

Off

False, and the controller scans the rung but does not execute it.
It takes only 1.4

µ

s to only scan the rung.

If I:000/02 is

Rungs 2 and 3 are

On

Skipped

Off

Executed

00

JMP

rung 1

B3:0

20

I:000

02

MVM

MVM

JMP

O:013

20

LBL

02

rung 2

rung 3

rung 4