Publication 1785-UM012D-EN-P - July 2005

Addressing I/O and Controller Memory 4-9

TIP

When assigning remote I/O rack numbers, use these
guidelines:

A single remote I/O scanner channel can support up to 32 devices
but only 16 rack numbers. For more information, see chapter 6.

Limit the number of remote I/O rack numbers to those that your
PLC-5 controller can support.

The PLC-5 controller and the 1771-ASB adapter module
automatically allocate the next higher rack number(s) to the
remaining I/O groups of the chassis. For example, if you select
1/2-slot addressing for your controller-resident local chassis and
you are using a 16-slot (1771-A4B) chassis, the controller will
address racks 0, 1, 2, and 3 in this chassis.

You can assign a remote I/O rack to a fraction of a chassis, a
single I/O chassis, or multiple I/O chassis as shown below.

01 23 45 67 01 23 45 67

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

16466

One 16-slot chassis, two racks

I/O Rack No. 0

One 16-slot chassis, one rack

One 8-slot chassis, 1/2 rack

Two 4-slot chassis, 1/4 rack each

I/O Rack No. 1

I/O Rack No. 3