Memory backup devices, Battery specifications, Eeprom compatibility – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 272

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

A-4 System Specifications

Battery Specifications

Enhanced and Ethernet PLC-5 programmable controllers use 1770-XYC
batteries that contain 0.65 grams of lithium.

Memory Backup Devices

You can add an EEPROM to the PLC-5 controller to provide backup memory
for your program in case the controller loses power. These memory cards are
available:

Use your programming software to save a program currently in the controller
to the EEPROM card. If you restore a program from the EEPROM to
controller memory and controller memory is bad, the restore changes the date
and time in the controller status file to the date and time the EEPROM was
saved. If you restore a program from the EEPROM to controller memory and
controller memory is valid, the status file retains its current date and time.

EEPROM Compatibility

EEPROM compatibility is related to:

Battery Life Estimates

In these Controllers

At this
Temperature

Power Off
100%

Power Off
50%

Battery Duration
Aafter the LED Lights

1

PLC-5/11B, -5/20B and -5/20E

60°C

256 days

1.4 years

11.5 days

25°C

2 years

4 years

47 days

PLC-5/30B -5/40B, -5/40E, -5/40L,
-5/60B, -5/60L, -5/80B and -5/80E

60°C

84 days

150 days

5 days

25°C

1 year

1.2 years

30 days

1

The battery indicator (BATT) warns you when the battery is low. These durations are based on the battery supplying the only power to the controller

(power to the chassis is off) once the LED first lights.

Catalog Number

For This Product

Memory Size

1785-ME16

Enhanced PLC-5 controllers

16K words

1785-ME32

Enhanced PLC-5 controllers

32K words

1785-ME64

Enhanced PLC-5 controllers

64K words

1785-ME100

Enhanced PLC-5 controllers

100K words