S:3-10 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 277

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

Processor Status File B-3

S:3-10

This Word

Stores

S:3 to S:6

Active Node table for channel 1A
WordBitsDH+ Station #
30-1500-17
40-1520-37
50-1540-57
60-1560-77

S:7

Global status bits: (See also S:27, S:32, S:33, S:34, and S:35)

• S:7/0-7

rack fault bits for racks 0-7

• S:7/8-15

unused

S:8

Last program scan (in ms)

S:9

Maximum program scan (in ms)

S:10Minor fault (word 1)
See also S:17

S:10/00

Battery is low (replace in 1-2 days)

S:10/01

DH+ active node table has changed

S:10/02

STI delay too short, interrupt program overlap

S:10/03

memory module transferred at power-up

S:10/04

Edits prevent SFC continuing; data table size changed during
program mode; reset automatically in run mode

S:10/05

Invalid I/O status file

S:10/06

reserved

S:10/07

No more command blocks exist to execute block-transfers

S:10/08

Not enough memory on the memory module to upload the program
from the controller

S:10/09

No MCP is configured to run

S:10/10

MCP not allowed

S:10/11

PII word number not in local rack

S:10/12

PII overlap

S:10/13

no command blocks exist to get PII

S:10/14

Arithmetic overflow

S:10/15

SFC “lingering” action overlap - step was still active when step
was reactivated