S:3-10 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
Page 277

Publication 1785-UM012D-EN-P - July 2005
Processor Status File B-3
S:3-10
This Word
Stores
S:3 to S:6
Active Node table for channel 1A
WordBitsDH+ Station #
30-1500-17
40-1520-37
50-1540-57
60-1560-77
S:7
Global status bits: (See also S:27, S:32, S:33, S:34, and S:35)
• S:7/0-7
rack fault bits for racks 0-7
• S:7/8-15
unused
S:8
Last program scan (in ms)
S:9
Maximum program scan (in ms)
S:10Minor fault (word 1)
See also S:17
S:10/00
Battery is low (replace in 1-2 days)
S:10/01
DH+ active node table has changed
S:10/02
STI delay too short, interrupt program overlap
S:10/03
memory module transferred at power-up
S:10/04
Edits prevent SFC continuing; data table size changed during
program mode; reset automatically in run mode
S:10/05
Invalid I/O status file
S:10/06
reserved
S:10/07
No more command blocks exist to execute block-transfers
S:10/08
Not enough memory on the memory module to upload the program
from the controller
S:10/09
No MCP is configured to run
S:10/10
MCP not allowed
S:10/11
PII word number not in local rack
S:10/12
PII overlap
S:10/13
no command blocks exist to get PII
S:10/14
Arithmetic overflow
S:10/15
SFC “lingering” action overlap - step was still active when step
was reactivated