9-16 Communicating with Devices on a DH+ Link

Average DH+ Link Response Time Test Results

This section shows graphically the results of testing performed on a DH+ link
where the number of stations and words sent in the message varies.

The figure below shows the average response time of messages of varying
sizes on a DH+ link with a varying numbers of stations. It also gives you an
idea of the typical response time you can expect on a given DH+ link.

Test Setup
One to 22 PLC-5 controllers were used with one
personal computer online. Each PLC-5 controller
executes 1K of ladder logic.
Initial testing was done with one PLC-5 controller
writing data to another PLC-5 controller. The
response time was recorded. Additional PLC-5
controllers were added to the network, each
writing the same amount of data to a PLC-5
controller at the next highest station address.
Four separate tests were run using data
transmissions of 50, 100, 250, and 500 words.

Number of PLC-5 Processors

Response

Time

(Sec)

50 W

100 W

250 W

500 W

+

X

W=Words

5.0

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

0.5

0.0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

+

+

+

+ +

+

+

+

+

+

X

X

X

X

X

X

X

X

X

X

Number of Controllers