Publication 1785-UM012D-EN-P - July 2005

B-4 Processor Status File

S:11

This Word

Stores

S:11major fault word

S:11/00

Corrupted program file (codes 10-19). See major fault codes (S:12).

S:11/01

Corrupted address in ladder program (codes 20-29). See major
fault codes (S:12).

S:11/02

Programming error (codes 30-49). See major fault codes (S:12).

S:11/03

Controller detected an SFC fault (codes (71-79). See major fault
codes (S:12).

S:11/04

Controller detected an error when assembling a ladder program
file (code 70); duplicate LBLs found.

S:11/05

Start-up protection fault. The controller sets this major fault bit
when powering up in Run mode if the user control bit S:26/1 is set.

S:11/06

Peripheral device fault

S:11/07

User-generated fault; controller jumped to fault routine (codes
0-9). See major fault codes (S:12).

S:11/08

Watchdog faulted

S:11/09

System configured wrong (codes 80-82, 84-88, 200-208). See
major fault codes (S:12).

S:11/10

Recoverable hardware error

S:11/11

MCP does not exist or is not a ladder or SFC file

S:11/12

PII file does not exist or is not a ladder file

S:11/13

STI file does not exist or is not a ladder file

S:11/14

Fault routine does not exist or is not a ladder file

S:11/15

Faulted program file does not contain ladder logic