Remote i/o system, Ethernet transmit led – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 354

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

F-6 Troubleshooting

Ethernet Transmit LED

The PLC-5 Ethernet interface contains an Ethernet Transmit LED that lights
(green) briefly when the Ethernet port is transmitting a packet. It does not
indicate whether or not the Ethernet port is receiving a packet.

Remote I/O System

Troubleshooting Guide for the 1771-ASB Series C and D
Adapter Module

BATT

PROC

FORCE

COMM

PROG

RUN

R

E

M

ENET

TRANSMIT

ACTIVE

ADAPTER

FAULT

I/O RACK

FAULT

Indicators

Description

Probable Cause

Recommended Action

Active

Adapter
Fault

I/O
Rack

On

Off

Off

Normal indication;
remote adapter is fully
operational

Off

On

Off

RAM memory fault, watchdog timeout Replace module.

On

Blink

Off

Module placement error I/O module in incorrect slot.

Place module in correct slot in chassis.

Blink in unison

Off

Incorrect starting I/O
group number

Error in starting I/O group number or
I/O rack address

Check switch settings.

On

On

On

Module not
communicating

Incorrect transmission rate setting

Off

On

On

Module not
communicating

Scan switch set for “all but last four
slots” in 1/4 rack

Reset scan switch setting.

Blink

Off

Off

Remote adapter not
actively controlling I/O
(scanner to adapter
communication link is
normal)

(1)

Controller is in program or test mode
Scanner is holding adapter module in
fault mode

Fault should be cleared by I/O scanner.

LEDs sequence on/off from
top to bottom

Module not
communicating

Another remote I/O adapter with the
same address is on the link.

Correct the address.

Advertising