Communicating with Remote I/O
Using This Chapter
This chapter explains how to configure the controller to communicate with
remote I/O:
1. Select which channel to configure as a scanner.
2. Define the I/O status file.
Use a unique, unused integer file. You must define an I/O status file if
you want to autoconfigure your system.
3. Define a diagnostic file.
Use a unique, unused integer file.
4. Define the scan list.
For Information About
Go to Page
Selecting devices that you can connect
Introduction to remote I/O
Designing a remote I/O link
Configuring a controller channel as a scanner
Communicating to a remote I/O node adapter
Transferring block data
Block-transfers of remote I/O data
Block-transfer sequence with status bits
Block-transfer programming considerations
Monitoring remote I/O scanner channels
Addressing the I/O status file