Publication 1785-UM012D-EN-P - July 2005

Communicating with Devices on a DH+ Link 9-3

For proper operation, terminate both ends of a DH+ link by using the
external resistors shipped with the programmable controller. Selecting either a
150

or 82

terminator determines how many devices you can connect on a

single DH+ link.

Configuring the Channel
for DH+ Communication

Depending on the controller you are using, you can configure
these channels:

IMPORTANT

If you select the baud rate as 230.4 kbps, and you are using
the serial port or a PLC-5 coprocessor, use channel 2 for
better overall system performance.

If Your DH+ I/O Link Operates at

Use this Resistor
Rating

230.4 kbps

82

57.6 kbps or 115.2 kbps

150

Controller

Channels that Support DH+

PLC-5/11

1A

PLC-5/20

1A (fixed DH+), 1B

PLC-5/30

PLC-5/40L

PLC-5/60L

PLC-5/20E

PLC-5/40E

PLC-5/80E

1A, 1B

PLC-5/40

PLC-5/60

PLC-5/80

1A, 2A, 1B, 2B

IMPORTANT

To define the DH+ address and baud rate for channel 1A,
you must set switch assembly SW1 on the controller;
you cannot set this node address through the programming
software.