Considerations for extended-local racks -8, Considerations for extended-local racks – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 126

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

8-8 Communicating with Extended-Local I/O

Example Calculations:
Here is an example system that provides sample calculations of a worst case
block-transfer completion time and the completion time of the modules in
chassis 2.

Considerations for Extended-local Racks

The following are programming considerations when you are transferring
block data in an extended-local rack:

Block-transfer instructions to any of the following modules that reside
in an extended-local rack will result in frequent checksum errors:

1771-OFE1, -OFE2, and -OFE3 modules, all versions prior to series

B, revision B

IMC-120 and IMC-123, all versions

The logic scan completes in 15 ms. Housekeeping completes in
approximately 6 ms (as calculated in the formula on page
NO TAG). The longest block-transfer request is 20 words.

Extended-Local I/O Link

PLC-5/40L
Processor

Channel 2

Processor-
Resident
I/O

No BT
modules

2 BT
modules

1 BT
modules

No BT
modules

Extended-Local I/O Chassis 1

Extended-Local I/O Chassis 2

Extended-Local I/O Chassis 3

1771-ALX
Adapter
Module

1771-ALX
Adapter
Module

1771-ALX
Adapter
Module

D (ms) = (2 2) (2) + (0.1 20 )]

D = 10 ms

T = 10 1

T = 10 ms

Worst-case time (T) = D X R

D = 2E L + (0.1W)

and

R = 1

Because 10 < 15 (which is the logic scan)

D (ms) = (2 2) (1) + (0.1 20 )]

D = 6 ms

T = 6 1

T = 6 ms

Completion time (T) for module in chassis 2 transfer: = D X R
Block-transfer length = 20

D = 2E M + (0.1W)

and

R = 1

Because 6 < 15 (which is the logic scan)

Advertising