S:79-s:127 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 286

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

B-12 Processor Status File

S:79-S:127

S:68

Installed memory card type:

0 - No memory card installed
1 - 1785-ME16
2 - 1785-ME32
3 - 1785-ME64
4 - 1785-ME100
5 - 1785-CHBM
6 - 1785-RC
7-15 - Reserved

When the 1785-RC module is installed, the eight least-significant

bits indicate the memory card’s status:
Bit 3 is set when the memory card is installed
Bit 2 is set when contact is detected closed
Bit 1 is set when the relay is driven open
Bit 0 is set when 120V ac is present on the memory card

When any other memory card is installed, the bits are undefined.

S:77

Communication time slice for communication housekeeping
functions (in ms)

S:78

MCP I/O update disable bits

Bit 0 for MCP A
Bit 1 for MCP B
etc.

This Word

Stores

This Word

Stores

S:79

MCP inhibit bits

Bit 0 for MCP A
Bit 1 for MCP B
etc.

S:80-S:127

MCP file number
MCP scan time (in ms)
MCP max scan time (in ms)

The above sequence applies to each MCP; therefore, each MCP
has
3 status words.

For example,word 80: file number for MCP A
word 81: scan time for MCP A
word 82: maximum scan time for MCP A
word 83: file number for MCP B
word 84: scan time for MCP B
etc.

Advertising