Controller communication channel troubleshooting – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 352

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

F-4 Troubleshooting

Controller Communication Channel Troubleshooting

Indicator Color

Channel Mode

Description

Probable Cause Recommended Action

A or B

Green
(steady)

Remote I/O Scanner Active Remote I/O link, all

adapter modules are
present and not faulted

Normal operation No action required

Remote I/O Adapter Communicating with

scanner

DH+

Controller is transmitting or
receiving on DH+ link

Green
(blinking
rapidly or
slowly)

Remote I/O Scanner At least one adapter is

faulted or has failed

• Power off at

remote rack

• Cable broken

• Restore power to

the rack

• Repair cable

DH+

No other nodes on network

Red
(steady)

Remote I/O Scanner
Remote I/O Adapter
DH+

Hardware fault

Hardware error

Turn power off, then on

Check that the software
configurations match the
hardware set-up

Replace the controller.

Red
(blinking
rapidly or
slowly)

Remote I/O Scanner All adapters faulted

• Cable not

connected or
broken

• Power off at

remote racks

• Repair cable

• Restore power to racks

DH+

Bad communication on DH+ Duplicate

node detected

Correct station address

Off

Remote I/O Scanner
Remote I/O Adapter
DH+

Channel offline

Channel is not
being used

Place channel online
if needed