Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 356

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

F-8 Troubleshooting

Troubleshooting Guide for the 1771-ASB Series C and D
Adapter Module (continued)

Indicators

Description

Probable Cause

Recommended Action

Active

Adapter
Fault

I/O
Rack

Off

Off

On

I/O chassis fault.

(1)

No communication
on link.

Problem exists between:

• adapter and module in chassis; the

module will stay in fault mode until
fault is corrected

• shorted printed circuit board runs on

backplane or I/O module

Cycle power to the chassis to clear a
problem resulting from high noise.

(2)

• Remove and replace all I/O modules one at a

time

• If problem does not clear, something is

wrong in chassis or I/O module

Blink

Off

On

Communication
on link.
Possible shorted
backplane

• Noise on backplane
• Shorted circuit board runs
• Faulty card in chassis

• Eliminate noise
• Isolate noise
• Add surge suppression
• Replace chassis
• Replace defective card in chassis

Blink

On

Off

Module identification
line fault

Excessive noise on backplane

Verify power supply and chassis grounding.

Off

Off

Off

Module not
communicating

Power supply fault

Wiring from scanner to adapter
module disrupted

Scanner not configured properly

One faulted chassis within a rack
group address causing
scanner/distribution panel to fault all
chassis in rack group address (when in
disable search mode)

Check power supply, cable connections,
and make sure adapter module is fully
seated in chassis.

Correct cable and wiring defects

See publication 1772-2.18 for scanner
configuration.

Check sequentially from the first module to
the last module to pinpoint fault; correct
any faults and proceed to the next chassis.

(1)

The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane.

(2)

Cycling power clears block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers.