D-19, Diagnostic instructions – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 319

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

Instruction Set Quick Reference D-19

Diagnostic Instructions

Instruction

Description

File Bit Compare
FBC

Status Bits:
EN - Enable
DN - Done Bit
ER - Error Bit
IN - Inhibit Bit
FD - Found Bit

When the input conditions go from false-to-true, the controller
compares the number of bits specified in the CMP Control
Length (48) of the Source file (#I:031) with the bits in the
Reference file (#B3:1). The controller stores the results
(mismatched bit numbers) in the Result file (#N7:0). File R6:4
controls the compare and file R6:5 controls the file that
contains the results. The file containing the results can hold up
to 10 (the number specified in the Length field) mismatches
between the compared files.

Note: To avoid encountering a possible run-time error when
executing this instruction, add a ladder rung that clears S:24
(indexed addressing offset) immediately before a FBC
instruction.

Diagnostic Detect
DDT

Status Bits:
EN - Enable
DN - Done Bit
ER - Error Bit
IN - Inhibit Bit
FD - Found Bit

When the input conditions go from false-to-true, the controller
compares the number of bits specified in the CMP Control
Length (20) of the Source file (# I:030) with the bits in the
Reference file (#B3:1). The controller stores the results
(mismatched bit numbers) in the Result file (#N10:0). Control
element R6:0 controls the compare and the control element
R6:1 controls the file that contains the results (#N10:0). The file
containing the results can hold up to 5 (the number specified in
the Length field) mismatches between the compared files. The
controller copies the source bits to the reference file for the
next comparison.

The difference between the DDT and FBC instruction is that
each time the DDT instruction finds a mismatch, the controller
changes the reference bit to match the source bit. You can use
the DDT instruction to update your reference file to reflect
changing machine or process conditions.

Note: To avoid encountering a possible run-time error when
executing this instruction, add a ladder rung that clears S:24
(indexed addressing offset) immediately before a DDT
instruction.

Data Transition
DTR

The DTR instruction compares the bits in the Source (I:002)
through a Mask (0FFF) with the bits in the Reference (N63:11).
When the masked source is different than the reference, the
instruction is true for only 1 scan. The source bits are written
into the reference address for the next comparison. When the
masked source and the reference are the same, the instruction
remains false.

FBC

FILE BIT COMPARE

Source

Result

#I:031

#N7:0

#B3:1

R6:4

Reference

Cmp Control
Length

Result Control

Position

48

0

Position

Length

R6:5

10

0

DDT

DIAGNOSTIC DETECT

Source

Result

#I:030

#N10:0

#B3:1

R6:0

Reference

Cmp Control
Length

Result Control

Position

20

0

Position

Length

R6:1

5

0

DTR

DATA TRANSITION

Source

Reference

I:002

N63:11

Mask

0FFF