Publication 1785-UM012D-EN-P - July 2005

F-2 Troubleshooting

PLC-5 Controller

General Problems

Indicator

Color

Description

Probable Cause

Recommended Action

PROC

Green
(steady)

Controller is in run mode and
fully operational

Normal operation

No action required

Green
(blinking)

Controller memory is being
transferred to EEPROM

Normal operation

No action required

Red
(blinking)

Major fault

• RSLogix 5

download in
progress

• Run-time error

During RSLogix 5 download, this
is normal operation - wait for
download to complete.

If not during RSLogix 5
download:

• Check major fault bit in status

file (S:11) for error definition

• Clear fault, correct problem, and

return to run mode

Alternating
Red and
Green

Controller in FLASH-memory
programming mode

Normal operation
if controller's
FLASH memory is
being
reprogrammed

No action required - allow flash
update to complete

Red

(steady)

Power cycle with problem
battery

Battery is low,
disconnected or
not installed

Properly replace or install
battery (see Chapter 1 for more
information)

Red

(steady)

Fault with memory loss

New controller

Invalid ControlNet
network address

Controller has
failed internal
diagnostics

Use programming software to
clear and initialize memory

Verify that ControlNet address
switch is not set to 0

Install battery (to preserve
failure diagnostics), then power
down, reseat controller and
power up; then reload your
program. If you are unable to
reload your program, replace the
controller. If you are able to
reload your program and fault
persists, contact Technical
Support at 440.646.6800 to
diagnose the problem.

Off

Controller is in program load or
test mode or is not receiving
power

Check power supply and
connections

BATT

PROC

FORCE

COMM

PROG

RUN

R
E

M