8-4 Communicating with Extended-Local I/O

You cannot configure more than one rack to have the same starting rack
number and module group; that is, you cannot use chassis to chassis
complementary I/O.

Follow these guidelines when you plan your extended-local I/O system.

Do not configure controller input interrupts (PIIs) for inputs in an
extended-local I/O chassis. The PII inputs must be in the
controller-resident local I/O rack.

You can either use 32-point I/O modules and any addressing method or
use 1771-IX or -IY modules and any addressing method in extended-
local I/O racks. You must specify the type of I/O modules you are
using by setting the configuration plug on the extended-local I/O
adapter.

If you need to use a thermocouple module and 32-point I/O modules in
the same I/O chassis, use the 1771-IXE module.

Transferring Data

The PLC-5/40L or -5/60L controller can scan controller-resident I/O,
extended local I/O, and remote I/O. The following figure shows how a
PLC-5/40L or -5/60L controller accomplishes I/O scanning and update.

PLC-5/40L and -5/60L I/O Scanning and Update

Input

Output

I/O Image Table

I/O Image Table Update
Synchronous to
program scan
(during housekeeping)

Remote I/O
Buffer Update
Asynchronous to
program scan

Extended
Local
I/O

Input

Output

Input
Output

Input
Output

Processor-
Resident
Local I/O

Remote I/O
Link

Remote
I/O
Buffer