Publication 1785-UM012D-EN-P - July 2005

Addressing I/O and Controller Memory 4-13

Addressing File Types

The following two tables show the available file types and the amount of
memory used by each.

Data Table File Types and Memory Usage for PLC-5 Controllers Series E/Revision D

and Later

File Type

File-Type
Identifier

File
Number

Maximum Size of File
16-bit Words and Structures

Memory Used in
Overhead for Each
File
(in 16-bit Words)

Memory Used
(in 16-bit Words)
per Word,
Character, or
Structure

PLC-5/11,
-5/20,
-5/20E

PLC-5/30 PLC-5/40,

-5/40E,
-5/40L

PLC-5/60,
-5/60L,
-5/80, -5/80E

Output image O

0

32

64

128

192

6

1/word

Input image

I

1

32

64

128

192

6

1/word

Status

S

2

128

128

128

128

6

1/word

Bit (binary)

B

3

1

2000 words

6

1/word

Timer

T

4

1

6000 words/2000 structures

6

3/structure

Counter

C

5

1

6000 words/2000 structures

6

3/structure

Control

R

6

1

6000 words/2000 structures

6

3/structure

Integer

N

7

1

2000 words

6

1/word

Floating-point F

8

1

4000 words/2000 structures

6

2/structure

ASCII

A

3-999

2000 words

6

1/2 per character

BCD

D

3-999

2000words

6

1/word

Block-transfer BT

3-999

12000 words/2000 structures

6

6/structure

Message

MG

3-999

32760 words/585 structures

2

6

56/structure

PID

PD

3-999

32718 words/399 structures

2

6

82/structure

SFC status

SC

3-999

6000 words/2000 structures

6

3/structure

ASCII string

ST

3-999

32760 words/780 structures

2

6

42/structure

Unused

--

9-999

6

6

0

1

This is the default file number and type. For this file type, you can assign any file number from 3 through 999.

2

The maximum size of a data table file is 32K words. The maximum size of the entire data table is 64K words