D-26 Instruction Set Quick Reference

Instruction

Description

Block Transfer Read
BTR

If the input conditions go from false to true, a block transfer
read is initiated for the I/O module located at rack 1, group 0,
module 0. The Control Block (BT11:100, 6-word file) contains
status for the transfer. The Data File (N10:110) is where the
data read from the module is stored. The BT Length (40)
identifies the number of words in the transfer. A non-continuous
block transfer is queued and run only once on a false-to-true
rung transition; a continuous block transfer is repeatedly
requeued.

You can also use the N data type for the control blocks.

See page F-8 for a description of prescan operation for
this instruction.

PLC-5/30, -5/40, -5/40E, -5/40L
-5/60, -5/60L, -5/80, -5/80E
controllers

PLC-5/40, -5/40L, -5/60,
-5/60L, -5/80, -5/40E,
-5/80E controllers

PLC-5/60, -5/60L,
-5/80, -5/80E controllers

S:7

bit #

BT queue

full for rack

S:32
bit #

BT queue

full for rack

S:34
bit #

BT queue

full for rack

08

(1)

0

08

10

08

20

09

1

1

09

11

09

21

10

1

2

10

12

10

22

11

1

3

11

13

11

23

12

4

12

14

12

24

13

5

13

15

13

25

14

6

14

16

14

26

15

7

15

17

15

27

(1)

PLC-5/11, -5/20, and 5/20E controllers also

Instruction

Description

Block Transfer Write
BTW

If the input conditions go from false-to-true, the block
transfer write is initiated for the I/O module located at rack
1, group 0, module 0. The Control Block (BT11:0, 6-word file)
contains status for the transfer. The Data File contains the
data to write to the module (N10:10). The BT Length (40)
identifies the number of words in the transfer. A
non-continuous block transfer is queued and run only once
on a false-to-true rung transition; a continuous block
transfer is repeatedly requeued. You can also use the N
data type for the control block.

See page f-8 for a description of prescan operation for this
instruction.

BTR

BLOCK TRANSFER READ

Rack

Module

1

0

0

BT11:100

Group

Control Block
Data File

Continuous

Length

N10:110

Y

40

BTW

BLOCK TRANSFER WRITE

Rack

Module

1

0

0

BT11:0

Group

Control Block
Data File

Continuous

Length

N10:10

Y

40