Publication 1785-UM012D-EN-P - July 2005

6-8 Communicating with Remote I/O

ATTENTION

Assign a unique diagnostic file to each channel. Do not
assign a diagnostic file that is the I/O status file you
assigned or any other used integer file. Unpredictable
machine damage can result.

In this Field

Define

By Doing the Following

Diagnostic file

The file containing the channel’s status
information:

messages received

messages sent

messages received with error

unable to receive

sent with error

rack retries

Cursor to the field, type an integer file number (9-999)

Baud rate

The communication rate for the remote
I/O scanner mode link

Cursor to the field and select the desired rate.Available rates are:
57.6, 115.2, and 230.4 kbps.

IMPORTANT

You must define a diagnostics file for a channel configured
for anything but unused (even if you are not using the
channel) if you want to get status information for that
channel.