Communicating with Remote I/O 6-25

Bit Layout Diagrams for the First Word Allotted to a Remote I/O Rack or an
Extended-Local I/O Rack

This Bit

Corresponds to

Fault Bits

00

first 1/4 rack
starting I/O group 0

01

second 1/4 rack
starting I/O group 2

02

third 1/4 rack
starting I/O group 4

03

fourth1/4 rack
starting I/O group 6

Present Bits

08

first 1/4 rack
starting I/O group 0

09

second 1/4 rack
starting I/O group 2

10

third 1/4 rack
starting I/O group 4

11

fourth1/4 rack
starting I/O group 6

00

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

Not Used

Not Used

Fault Bits

Present Bits

N15:14