Allowing or inhibiting startup, Defining a controller power-up procedure – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 236

Advertising
background image

Publication 1785-UM012D-EN-P - July 2005

14-2 Preparing Power-Up Routines

Allowing or Inhibiting
Startup

Major fault bit S:11/5 controls whether you can power up the controller in run
mode after a loss of power. Do not confuse this bit with user control bit
S:26/1.

After a power loss is experienced while the controller is in run mode, the
controller automatically sets major fault bit S:11/5 if user control bit S:26/1
has been set.

Defining a Controller
Power-Up Procedure

The user control bits S:26/0 and S:26/1 define how the controller starts in run
mode after a power loss or when you switch to run mode from program or test
mode.

This Bit

Tells the Controller

user control
S:26/1

whether or not to scan a fault routine upon power up before
returning to normal program scan.

major fault S:11/5 whether or not to fault at the end of scanning the fault routine.

If the Fault Routine
Makes S:11/5

Then the Controller

Set (1)

Faults at the end of scanning the fault
routine
Leave this bit set to inhibit startup

Reset (0)

Resumes scanning the controller memory file
Reset this bit to allow startup

IMPORTANT

You can use JMP and LBL instructions to scan only the
portion of the fault routine associated with a particular
fault or power-up condition.