Communicating with Devices on a Serial Link 10-15

This Field

Specifies

Configure by Doing the Following

Master message
transmit

The current value of channel 0 master
message transmit

If you want the master station to:

send all of the master station-initiated MSG instructions to the remote
stations before polling the next remote station in the poll list, choose
Between Station Polls

This method makes certain that master station-initiated messages are
sent in a timely and regular manner (after every remote station poll).

only send master station-initiated MSG instructions when the master’s
station number appears in the polling sequence, choose In Poll Sequence

With this method, sending master station-initiated messages are
dependent upon where and how often the master station appears in the
poll list. To achieve the same goal as the Between Station Polls method,
the master-station’s address would have to appear after every
remote-station’s address.

The controller sets a minor fault if you are using IN POLL SEQUENCE and
the master’s station is not in either the normal poll list or the priority
poll list.

Normal poll node file

The integer file that contains the
addresses of the remote stations you
want in the normal poll list

Enter an integer file number 0-255

Normal poll group size The quantity of active stations located

in the normal poll list that you want
polled during a scan through the
normal poll list before returning to the
priority poll list

Enter a valid value 10-999.

Priority poll node file

The integer file that contains the
addresses of the remote stations you
want in the priority poll list

Enter an integer file number 10-999.

Active station file

The binary file that stores the station
addresses of all active stations on
the link.

Enter a binary file number 10-999.