Example of a group process at work, Put it all together – MTS Series 793 Application User Manual

Page 158

Advertising
background image

MTS MultiPurpose TestWare®

Determine Which Processes Are Needed

Creating a Practice Test Procedure

158

Example of a group

process at work

The following illustrates Step 4.

Put it all together

All of the processes required to perform the activities in the sample test sketch
are shown below in the process diagram.

75

°

50

°

On

Off

1. The first Data Limit

process detects when
the physical specimen’s
temperature reaches
75

°

C.

The Group process holds the
individual processes used to control
the cooling fan.

2. The first Digital Output

process sends out a
pulse that turns the fan
on when the physical
specimen’s temperature
reaches 75

°

C.

3. The second Data

Limit process
detects when the
physical specimen’s
temperature drops
to 50

°

C.

1

2

3

4

4. The second Digital

Output process turns
the fan off when the
physical specimen’s
temperature drops to
50

°

C, then the Group

process starts over
with the first Data Limit
process.

Advertising