Advanced Features

Chapter 9

9-6

low for the specified duration when triggered to pulse

When an output changes to a high or low state, it is guaranteed to stay in
that state for a minimum of 16 milliseconds in order to be compatible with
the discrete inputs. Thus if two successive changes to an output are
initiated within 16 milliseconds of each other, the second change will be
delayed until the 16 millisecond interval has expired. If the second change
is a pulse, the duration of that pulse will also be shortened by the length of
the additional delay.

Figure 9.4

Programmable I/O Control Word

50089

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

0

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

Programmable

OUTPUT 1 pulse

duration:

INPUT 2 trigger:

00 = High level

01 = Low level

10 = Positive edge

11 = Negative edge

0

0

Normal/complement

(0/1) programmable

OUTPUT 1

Programmable

OUTPUT 2 pulse

duration:

Normal/complement

(0/1) programmable

OUTPUT 2

Programmable outputs

reset/fault state:

0 = Last state

1 = Reset

INPUT 1 trigger:

00 = High level

01 = Low level

10 = Positive edge

11 = Negative edge

OUTPUT 2:

0 = Loop Fault

1 = Programmable

OUTPUT 1:

0 = InĆposition

1 = Programmable

00 20 ms

01 50 ms

10 100 ms

11 200 ms

Bits 4 and 5 - OUTPUT 2 Pulse Duration

If OUTPUT 2 is configured to be programmable and motion segment
control word 2 specifies that OUTPUT 2 is pulsed when trigger conditions
are satisfied, these bits define the duration of the pulse to be 20, 50, 100 or
200 milliseconds.