Hardware Description

Chapter 4

4Ć6

Figure 4.3

Simplified Schematic of a Discrete Input

50041

1771 - QB MODULE

27

INPUT SUPPLY

28

DISCRETE INPUT

(e.g. JOG FWD)

INPUT COMMON

+ 5V

10K

3.3K

Auto/Manual Input

The module accepts the signal at the AUTO/MAN terminal (13/14) as the
auto/manual input. Use this input in conjunction with block transfers to set the
operation mode for the axis. A high input means auto mode and a low input
means manual mode. The auto/manual input defaults to auto mode if the inputs
are disabled via the parameter block.

Important: To set the mode of the axis to auto, you must set both the
auto/manual input and the auto/manual bit in the command block high. If either
the bit or the input is low, the mode is manual.

Hardware Start Input

In the auto mode, the module accepts a transition from low to high at the
START terminal (15/16) as a high-true hardware start input signal.

If the axis is in auto mode, and if the hardware start has been enabled via the
command block, the module waits for a transition from low to high at the
START terminal before it will start axis movement to a previously commanded
setpoint. If you don’t want to use this feature, disable the hardware start via the
command block.

Important: Because of the module’s built-in switch debouncing, the
low-to-high transition must follow a minimum 16 ms low signal.