Status block appendix b – Rockwell Automation 1771-QB Linear Pos. User Manual
Page 182

Status Block
Appendix B
BĆ8
Table B.A
Error Codes
Code
Definition
00
No errors detected
01
Invalid block identifier
02
NonĆBCD number entered
03
Invalid bit setting, unused bits must be set to zero
04
Data is out of range
05
Invalid number of axes programmed
06
Setpoint is not defined
07
Setpoint commanded while in manual mode
08
Position exceeds a software overtravel limit
09
Attempted to switch to auto mode with axis in motion
10
Attempted to switch to manual mode with axis in motion
11
Velocity exceeds maximum
12
High jog rate > maximum velocity
13
Low jog rate > high jog rate
14
Maximum PID error must be outside the PID band
15
Incorrect block length
16
First block after powerup must be a parameter block
17
Negative travel limit > positive travel limit
18
Jog commanded while in auto mode
19
Forward and reverse jogs commanded simultaneously
20
Block transfer write attempted before module confirmed all power on wiring arm
21
Specified velocity exceeds maximum velocity for direction of motion
22
Motion segment ID not defined
23
Motion segment commanded while in manual mode
24
A motion segment is attempting to use an output which is not configured as a
programmable output
25