Status block appendix b – Rockwell Automation 1771-QB Linear Pos. User Manual

Page 182

Advertising
background image

Status Block

Appendix B

BĆ8

Table B.A

Error Codes

Code

Definition

00

No errors detected

01

Invalid block identifier

02

NonĆBCD number entered

03

Invalid bit setting, unused bits must be set to zero

04

Data is out of range

05

Invalid number of axes programmed

06

Setpoint is not defined

07

Setpoint commanded while in manual mode

08

Position exceeds a software overtravel limit

09

Attempted to switch to auto mode with axis in motion

10

Attempted to switch to manual mode with axis in motion

11

Velocity exceeds maximum

12

High jog rate > maximum velocity

13

Low jog rate > high jog rate

14

Maximum PID error must be outside the PID band

15

Incorrect block length

16

First block after powerup must be a parameter block

17

Negative travel limit > positive travel limit

18

Jog commanded while in auto mode

19

Forward and reverse jogs commanded simultaneously

20

Block transfer write attempted before module confirmed all power on wiring arm

21

Specified velocity exceeds maximum velocity for direction of motion

22

Motion segment ID not defined

23

Motion segment commanded while in manual mode

24

A motion segment is attempting to use an output which is not configured as a

programmable output

25

Motion segment ID previously defined in same motion block

Advertising