Installing the Linear Positioning Module

Chapter 5

5Ć18

The analog outputs provide the current (or voltage) by which the module
controls the servo valve. By controlling the servo valve, the module controls
axis motion.

ATTENTION: Applying output to an axis with polarity reversed can
cause sudden high-speed motion. For maximum safety, leave the
analog outputs disconnected and the axis power off until you perform
the axis tuning procedures in Chapter 8.

Figure 5.11

Analog Output Connections

Belden 8761 or equivalent (200 ft. max.)

Belden 8723 or equivalent (50 ft. max.)

3

50031

5

+ANALOG

-ANALOG

±

15 COMMON

Wiring Arm

Terminals

30

32

34

LOOP 2

29

31

33

35

LOOP 1

+ANALOG

-ANALOG

+15 VDC

-15 VDC

Ground the shield

at the I/O chassis end.

SERVO VALVE

LOOP 2

3

±

15 VDC

Analog Power

Supply

(Customer Supplied)

+ Comm -

Ground the shield

at the I/O chassis end.

Ground the common

at the I/O chassis end.

+15

-15

5

A

B

C

D

SERVO VALVE

LOOP 1

A

B

C

D

3

Ground the shield

at the I/O chassis end.

Connecting the Analog

Outputs