Installing the Linear Positioning Module
Chapter 5
5Ć18
The analog outputs provide the current (or voltage) by which the module
controls the servo valve. By controlling the servo valve, the module controls
axis motion.
ATTENTION: Applying output to an axis with polarity reversed can
cause sudden high-speed motion. For maximum safety, leave the
analog outputs disconnected and the axis power off until you perform
the axis tuning procedures in Chapter 8.
Figure 5.11
Analog Output Connections
Belden 8761 or equivalent (200 ft. max.)
Belden 8723 or equivalent (50 ft. max.)
3
50031
5
+ANALOG
-ANALOG
±
15 COMMON
Wiring Arm
Terminals
30
32
34
LOOP 2
29
31
33
35
LOOP 1
+ANALOG
-ANALOG
+15 VDC
-15 VDC
Ground the shield
at the I/O chassis end.
SERVO VALVE
LOOP 2
3
±
15 VDC
Analog Power
Supply
(Customer Supplied)
+ Comm -
Ground the shield
at the I/O chassis end.
Ground the common
at the I/O chassis end.
+15
-15
5
A
B
C
D
SERVO VALVE
LOOP 1
A
B
C
D
3
Ground the shield
at the I/O chassis end.
Connecting the Analog
Outputs