Formatting Module Data (WRITES)

Chapter 7

7Ć3

Parameter Control Word (word 1)

The parameter control word identifies the block as a parameter block and
provides configuration information common to both loops. You can also disable
the transducer interface, analog outputs, and discrete inputs by setting the
appropriate bits. If all three sections are disabled, you can test the
programmable controller program without connecting the wiring arm to the
module. Unused sections do not have to be powered.

Figure 7.2

Parameter Block Control Word

50001

Binary Position Format:

0 = Double Word

1 = Single Word

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

1

0

0

0

0

0

Transducer Interface:

0 = Enabled

1 = Disabled

Analog Outputs:

0 = Enabled

1 = Disabled

Discrete Inputs:

0 = Enabled

1 = Disabled

Axes used:

01 = Axis 1

10 = Axis 2

11 = Both axes

Units:

0 = Inch

1 = Metric

Format:

0 = Binary

1 = BCD

..

.

..

.
...

Identifies this as a

Parameter Block

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

0

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

Stop/Start Enhancement:

0 = Disabled

1 = Enabled

Bits 0 and 1 – Axes Used

Bits 0 and 1 determine which axes are controlled by the module. You can use
either one separately, or both. The module performs error processing
independently for each axis. If it detects a format error for one axis, it discards
all new parameters for that axis.

Bit 2 – Inch/metric

Bit 2 selects between metric and imperial units.