Installing the Linear Positioning Module

Chapter 5

5Ć13

Make sure that the voltage driving each input is at the appropriate level.
Figure 5.8 shows the discrete input connections.

Figure 5.8

Discrete Input Connections

50049

Auto/Manual

Wiring Arm

Terminals

14

16

18

20

22

24

26

28

LOOP 2

13

15

17

19

21

23

25

27

LOOP 1

Belden 8761 or equivalent (50 ft. max.)

15 to 24 VDC

Discrete Input

Supply

(Customer

Supplied)

- +

Start

Use any number of

EĆstop switches in series

Jog Forward

Jog Reverse

Input 1

Input 2

AUTO/MAN

START

STOP

JOG FWD

JOG REV

INPUT 1

INPUT 2

I/P COMMON

AUTO/MAN

START

STOP

JOG FWD

JOG REV

INPUT 1

INPUT 2

I/P SUPPLY

Auto/Manual

Start

Use any number of

EĆstop switches in series

Jog Reverse

Input 1

Input 2

Jog Forward

2

2

2

2

If you are driving a discrete input from a discrete output of another module,
keep in mind that you must measure the output voltage at the discrete output
itself and not at the discrete output power supply. There is a 1.6 VDC drop
between the power supply and the discrete output at maximum current. To yield
the minimum 10 VDC at the discrete output, the discrete output supply must be
greater than 11.6 VDC.