4 - hardware description, Indicators, Hardware description – Rockwell Automation 1771-QB Linear Pos. User Manual

Page 30

Advertising
background image

Chapter

4

4Ć1

Hardware Description

This chapter describes the Linear Positioning Module hardware, as well as other
hardware required for a positioning system.

Figure 4.1 shows the three indicators on the module.

Figure 4.1

Indicators

50009

LINEAR

POSITIONING

FAULT
LOOP1

ACTIVE
LOOP2

ACTIVE

When you first power up the module, all three indicators turn on for about one
second. Next, the LOOP 1 ACTIVE and LOOP 2 ACTIVE indicators turn off
while the module performs diagnostics. If the diagnostics discover a module
fault, the red FAULT indicator stays on and the module remains inactive. When
the programmable controller is in run mode, the indicators behave as follows:

FAULT - a red indicator that is normally off. The indicator turns on if there

is a module fault in one loop or both loops. See Chapter 11 for more
information on module faults.

LOOP 1 ACTIVE - a green indicator that is on when loop 1 is active. The

indicator blinks if a fault occurs on loop 1 and turns off if loop 1 is inactive.

LOOP 2 ACTIVE - a green indicator that is on when loop 2 is active. The

indicator blinks if a fault occurs on loop 2 and turns off if loop 2 is inactive.

Indicators