Interpreting ModuleĆtoĆPLC Data

(READS)

Chapter 6

6Ć3

Figure 6.2

Module Configuration Word

50001

Binary Position Format:

0 = Double Word

1 = Single Word

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

0

0

0

0

0

Transducer Interface:

0 = Enabled

1 = Disabled

Analog Outputs:

0 = Enabled

1 = Disabled

Discrete Inputs:

0 = Enabled

1 = Disabled

Axes used:

01 = Axis 1

10 = Axis 2

11 = Both axes

Units:

0 = Inch

1 = Metric

Format:

0 = Binary

1 = BCD

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

0

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

..

.

..

.
...

Stop/Start Enhancement:

0 = Disabled

1 = Enabled

0

Status Word 1 (words 2 and 6)

Each bit in status word 1 corresponds to a particular axis condition.

Bit 0 – Ready

The module turns off the ready bit after powerup or after a reset command. (See
Chapter 7.) The module turns this bit on when it receives a valid parameter
block for this loop. Unless it detects a fault, the module enables the analog
output for the axis when the ready bit turns on.

The module does not accept setpoint, motion or command blocks until the ready
bit is on.