Interpreting modulećtoćplc data (reads) chapter 6 – Rockwell Automation 1771-QB Linear Pos. User Manual

Page 72

Advertising
background image

Interpreting ModuleĆtoĆPLC Data

(READS)

Chapter 6

6Ć11

Table 6.A

Error Codes

Code

Definition

00

No errors detected

01

Invalid block identifier

02

NonĆBCD number entered

03

Invalid bit setting, unused bits must be set to zero

04

Data is out of range

05

Invalid number of axes programmed

06

Setpoint is not defined

07

Setpoint commanded while in manual mode

08

Position exceeds a software travel limit

09

Attempted to switch to auto mode with axis in motion

10

Attempted to switch to manual mode with axis in motion

11

Velocity exceeds maximum

12

High jog rate > maximum velocity

13

Low jog rate > high jog rate

14

Maximum PID error must be outside the PID band

15

Incorrect block length

16

First block after powerup must be a parameter block

17

Negative travel limit



positive travel limit

18

Jog commanded while in auto mode

19

Forward and reverse jogs commanded simultaneously

20

Block transfer write attempted before module confirmed all power on wiring arm

21

Specified velocity exceeds maximum velocity for direction of motion

22

Motion segment ID not defined

23

Motion segment commanded while in manual mode

24

A motion segment is attempting to use an output which is not configured as a

programmable output

25

Motion segment ID previously defined in same motion block

Position Information (words 4, 5; 8, 9; 12, 13; and 14, 15)

The position words give the present position measured at the transducer. The
position information is in either BCD or binary format. You choose the format
you want through the parameter block. Binary format is compatible with integer
data (16-bit 2’s complement) used by PLC-5 family programmable controllers.
See Appendix H for an explanation of numbering formats.

The maximum position displayed is

±

799.900 inches or

±

7999.00 millimeters.

If the status words 4, 5 and 8, 9 are specified in the command block to display
position, when the axis exceeds the maximum, the maximum is displayed and
the position valid bit in the second status word turns off.