Rockwell Automation 1771-QB Linear Pos. User Manual

Page 70

Advertising
background image

Interpreting ModuleĆtoĆPLC Data

(READS)

Chapter 6

6Ć9

Bit 13 – Feedback Fault

The feedback fault bit turns on when the module detects a fault in the transducer
interface circuitry. In this event, the module also activates OUTPUT 2 if
configured as the loop fault output. The following conditions will cause a
feedback fault:

loss of transducer power

internal loop-back fault

excessive change in velocity

loss of feedback

position exceeds maximum transducer length

Bit 14 – Analog Fault

The analog fault bit turns on when the module detects a fault in the analog
circuitry. In this event, the module also activates OUTPUT 2 if configured as
the loop fault output. The following conditions will cause an analog fault:

loss of analog power

analog power supply voltage out of tolerance

analog circuitry fault

Bit 15 – Internal Fault

The internal fault bit turns on if the module detects a fault in the circuitry
powered by the backplane. In this event, the module also activates OUTPUT 2
if configured as the loop fault output. If this fault occurs, return the module to
your Allen-Bradley representative.

Position/Error/Diagnostic Words

You can use these words to display diagnostic information, current axis
position, or the following error. You select the information to be displayed
through bits in the command block. You can also view all three parameters
simultaneously by specifying diagnostics for words 4, 5 and 8, 9; position
information for words 12, 13 and 14, 15; and following error for words 16, 17
and 18, 19. These selections use the extended status information. See Chapter 7
for details on the command block.